System Functions: SIlo Safety System.

Input Signals
1. SIlo High Level.
2. Silo High Level Healthy.
3.Silo High Pressure (Mechanical Pressure Switch)
4. Silo PRV Fault
5. Air Pressure Healthy.

Output Signals
6. Sounder/Beacon.
7. Silo Top FIlter.
8. Silo FIll Butterfly Valve.

If the systems gets a fault signal  from input signals 2/3/4/5 the system will shut 
immediately, if it gets a signal from item 1 there is a 45 sec delay, during this time the 
beacon will alarm and flash and the system will shut down."

 